Arc-Fault
Circuit Interrupters (AFCIs)
by Nick Gromicko and Kenton Shepard
Arc-fault
circuit interrupters (AFCIs) are special types of electrical receptacles or
outlets and circuit breakers designed to detect and respond to potentially
dangerous electrical arcs in home branch wiring.
How do they work?
AFCIs
function by monitoring the electrical waveform and promptly opening
(interrupting) the circuit they serve if they detect changes in the wave
pattern that are characteristic of a dangerous arc. They also must be capable
of distinguishing safe, normal arcs, such as those created when a switch is
turned on or a plug is pulled from a receptacle, from arcs that can cause
fires. An AFCI can detect, recognize, and respond to very small changes in wave
pattern.
What is an arc?
When
an electric current crosses an air gap from an energized component to a
grounded component, it produces a glowing plasma discharge known as an arc. For
example, a bolt of lightning is a very large, powerful arc that crosses an
atmospheric gap from an electrically charged cloud to the ground or another
cloud. Just as lightning can cause fires, arcs produced by domestic wiring are
capable of producing high levels of heat that can ignite their surroundings and
lead to structure fires.
According to statistics from the National Fire Protection Agency for the year 2005, electrical fires damaged approximately 20,900 homes, killed 500 people, and cost $862 million in property damage. Although short-circuits and overloads account for many of these fires, arcs are responsible for the majority and are undetectable by traditional (non-AFCI) circuit breakers.
Where are arcs likely to form?
Arcs
can form where wires are improperly installed or when insulation becomes
damaged. In older homes, wire insulation tends to crystallize as it ages,
becoming brittle and prone to cracking and chipping. Damaged insulation exposes
the current-carrying wire to its surroundings, increasing the chances that an
arc may occur.
Situations in which arcs may be created:
- electrical cords damaged by vacuum cleaners or trapped beneath furniture or doors.
- damage to wire insulation from nails or screws driven through walls.
- appliance cords damaged by heat, natural aging, kinking, impact or over-extension.
- spillage of liquid.
- loose connections in outlets, switches and light fixtures.
Where
are AFCIs required?
Locations
in which AFCIs are required depend on the building codes adopted by their
jurisdiction.
The 2006 International Residential Code (IRC) requires that AFCIs be installed within bedrooms in the following manner:
E3802.12 Arc-Fault
Protection of Bedroom Outlets. All branch circuits that supply120-volt,
single-phase, 15- and 20-amp outlets installed in bedrooms shall be protected
by a combination-type or branch/feeder-type arc-fault circuit interrupter
installed to provide protection of the entire branch circuit.
Exception:
The location of the arc-fault circuit interrupter shall be permitted to be at
other than the origination of the branch circuit, provided that:
1.
The
arc-fault circuit interrupter is installed within 6 feet of the branch circuit
overcurrent device as measured along the branch circuit conductors, and
2.
The
circuit conductors between the branch circuit overcurrent device and the arc-fault
circuit interrupter are installed in a metal raceway or a cable with metallic
sheath.
The
National Electrical Code (NEC) offers the following guidelines concerning AFCI
placement within bedrooms:
Dwelling Units. All
120-volt, single phase, 15- and 20-ampere branch circuits supplying outlets
installed in dwelling unit in family rooms, dining rooms, living rooms,
parlors, libraries, dens, sun rooms, recreation rooms, closets, hallways, or
similar rooms or areas shall be protected by a listed arc-fault circuit
interrupter, combination-type installed to provide protection of the branch
circuit.
Home
inspectors should refrain from quoting exact code in their reports. A
plaintiff's attorney might suggest that code quotation means that the inspector
was performing a code inspection and is therefore responsible for identifying
all code violations in the home. Some jurisdictions do not yet require
their implementation in locations where they can be helpful.
What
types of AFCIs are available?
AFCIs
are available as circuit breakers for installation in the electrical
distribution panel.
Nuisance
Tripping
An
AFCI might activate in situations that are not dangerous and create needless
power shortages. This can be particularly annoying when an AFCI stalls power to
a freezer or refrigerator, allowing its contents to spoil. There are a few
procedures an electrical contractor can perform in order to reduce potential
“nuisance tripping," such as:
- Check that the load power wire, panel neutral wire and load neutral wire are properly connected.
- Check wiring to ensure that there are no shared neutral connections.
- Check the junction box and fixture connections to ensure that the neutral conductor does not contact a grounded conductor.
Arc
Faults vs. Ground Faults
It
is important to distinguish AFCI devices from Ground Fault Circuit Interrupter
(GFCI) devices. GFCIs detect ground faults, which occur when current leaks from
a hot (ungrounded) conductor to a grounded object as a result of a
short-circuit. This situation can be hazardous when a person unintentionally
becomes the current’s path to the ground. GFCIs function by constantly
monitoring the current flow between hot and neutral (grounding) conductors, and
activate when they sense a difference of 5 milliamps or more. Thus, GFCIs are
intended to prevent personal injury due to electric shock, while AFCIs prevent
personal injury and property damage due to structure fires.
In summary, AFCIs are designed to detect small arcs of electricity before they have a chance to lead to a structure fire.
Thanks for Reading this article
brought to you by
John M. Wickline, President
![JW Home Inspections, Inc. Hilton Head, SC Home Inspector Hilton Head Bluffton Beaufort Sun City Okatee](https://blogger.googleusercontent.com/img/b/R29vZ2xl/AVvXsEi4YlikRsmSOM0coVlwhvOOZM2vo7V9vjYCL_Xlwr3ejjZCBaHACcyAJhy3-FLxlkW9EgdJYgaAHvFVF9G1w6hi8qk2B8JkpxpksUiscksn4zu-IaD-K2501oQqukR-9xg_TPpFRbC0UinV/s1600/JW+Home+Inspections+Inc+Logo+Hilton+Head+SC.jpg)
No comments: